23 May 2001, 21:09 UTC
Fort Pierce--Maximum Gas Consumtion for Planning Purposes
- From
- Mike Coleman mike.coleman@enron.com
- Cc
- Mark Breese, Ruth Concannon, Mathew Gimble, Darrell Stovall, Jeffrey Keenan, douglas.ottens@enron.com, Jennifer Bagwell
- Bcc
- Mark Breese, Ruth Concannon, Mathew Gimble, Darrell Stovall, Jeffrey Keenan, douglas.ottens@enron.com, Jennifer Bagwell
- Date
- Wed, 23 May 2001 14:09:56 -0700 (PDT)
Charlie, The new plant max consumption for planning purposes should be set at 2,490 mmBtu/hr HHV. In addition to this it is estimated that the existing Frame 5 may require 335 mmBtur/hr HHV, or a total of 2,825 mmBtu/hr HHV. The plant consumption is based on the maximum combustion turbine requirement, plus a 5% margin, plus duct burning requirement. This should be adequate as a conservative maximum case. Please let me know if you have any questions. Thanks! Mike Coleman