Thanks Mike.  Would you mind providing the MW and heat rate assumptions that correspond to these flows just for information purposes.


Thanks,

Charlie
Quoted or forwarded from earlier messages
-----Original Message-----
From: 	Coleman, Mike  
Sent:	Wednesday, May 23, 2001 4:10 PM
To:	Weldon, V. Charles
Cc:	Breese, Mark; Concannon, Ruth; Gimble, Mathew; Stovall, Darrell; Keenan, Jeffrey; Ottens, Douglas; Bagwell, Jennifer
Subject:	Fort Pierce--Maximum Gas Consumtion for Planning Purposes

Charlie,

The new plant max consumption for planning purposes should be set at 2,490 mmBtu/hr HHV.  In addition to this it is estimated that the existing Frame 5 may require 335 mmBtur/hr HHV, or a total of 2,825 mmBtu/hr HHV.

The plant consumption is based on the maximum combustion turbine requirement, plus a 5% margin, plus duct burning requirement.  This should be adequate as a conservative maximum case.

Please let me know if you have any questions.

Thanks!

Mike Coleman