ERCOT Message: New South to North Line Limits
- From
- D Eric Smith d.smith@enron.com
- Date
- Thu, 24 May 2001 08:50:00 -0700 (PDT)
Here is a message that came in from ERCOT. Due to the size of the message, it seems to have choked the database. I will fix that problem but in the meantime, here is the text of the message in case it is important information for you guys. ; The completion of the Limestone-Watermill 345 double circuit has made a significant change in the North/South interchange flows.; Previously a set of limits was calculated daily by ERCOT.; With the new transmission lines the old calculation is no longer valid.; ERCOT is now observing the South-North transfer as affected by the ATC calculator.; At this time we have adopted a set of not to exceed limits for the major 345 circuits in the transfer path.; These limits are: ; Good Weather ; Trading House-Venus 345 kv Double Circuit;;;;;;;;;;;;;;;;;;;;;;;; 1260 MVA Jewet-Big Brown 345 kv Double Circuit;;;;;;;;;;;;;;;;;;;;;;;;;;;; 1200 MVA Limestone-Watermill 345 kv Double Circuit;;;;;;;;;;;;;;;;;;;;;;;; 1500 MVA ; All Bad Weather & North; ; Trading House-Venus 345 kv Double Circuit;;;;;;;;;;;;;;;;;;;;;;;;; 750 MVA Jewet-Big Brown 345 kv Double Circuit;;;;;;;;;;;;;;;;;;;;;;;;;;;; 1200 MVA Limestone-Watermill 345 kv Double Circuit;;;;;;;;;;;;;;;;;;;;;;;; 1400 MVA ; Direct comments or questions about this posting to Lee Caylor at 512-225-7136. ; ; ; D. Eric Smith Enron Corp. Sr. Spec - IT Dev Tel: 713-345-8290 Pg: 713-288-3969 Email: d.eric.smith@enron.com ;