Larry, This looks like all of the comments. Jon
Quoted or forwarded from earlier messages
-----Original Message-----
From: Larry.Campbell@enron.com [mailto:Larry.Campbell@enron.com]
Sent: Tuesday, October 09, 2001 3:57 PM
To: Ruth.Jensen@enron.com; William.Kendrick@enron.com;
jfields@argentinc.com
Subject: TW Comments to air permits for Stat3 and 4
Jon and Ruth, presented below are the comments to the air perimts at 3 and
4. Please review for clairty and content. I have spoken to Roger Kohn
about all of these issues and the only one which may be a problem is with
No. 2. He is checking on what the EPA can do about this. I have spoken to
Arnold Eisenstein about what we can do with the strict 25 ppmvd requriement
for NOx and CO and he has said that we can hold to the 25 ppm value by
doing some major gas recycling. This is a fuel waste and costly. Anyway,
depending upon how long this issue delays the issuance of the permit will
undoubtably determine whether we give in to the 25 ppmvd or hold out for 40
ppmvd. Id like your comments asap.
1. The responsible official name change to Danny
Pribble.
2.. The draft permit limits NOx and CO emissions
to 25 ppmv at 15% O2, based on a 3-hour average, except during periods of
startup and shutdown. At 60F and above the GE data indicates that
these rates are achievable under all operating conditions. However, GE
data indicates that NOx and CO may be as high as 40 ppmv during
low-load conditions of 60%and lower.
The permit application represented turbine operations at base
load 80% of the time with reduced load operations (64% load)
occurring no more than 20% of the time. The potential to emit
calculations presented the emissions in the application in units of
lb.hr and ton/yr. These values were accepted by the EPA for
the netting analysis, and took were taken into account by the EPA
(See EPA Statement of Basis document). Because the permit
conditions hold us to ppmvd values and not lb/yr or ton/year
values, Transwestern is concerned that under low load
conditions of less than 60%, the emissions of NOx and CO would be
40 ppmvd. Transwestern is requesting that a provision be
made in the permit conditions that emissions of NOx and CO be held
to 40 ppmvd during the 20 % of the time that the turbines
operating conditions is less than or equal to 60%.
3. The word "Catepillar" is mispelled throughout the permit.
4. Permit conditions for sulfur testing in the fuel gas
requires Transwestern to use methodologies (wet chemistry
technology) that are not normally used to monitor and
measure sulfur in the natural gas. Transwestern has received
approval from the EPA for other custom fuel monitoring
schedules to use "GPA Standard 2377" (length of stain tube) or gas
chromatography as the proposed methodology to monitor sulfur in
the natural gas.
**********************************************************************
This e-mail is the property of Enron Corp. and/or its relevant affiliate and
may contain confidential and privileged material for the sole use of the
intended recipient (s). Any review, use, distribution or disclosure by
others is strictly prohibited. If you are not the intended recipient (or
authorized to receive for the recipient), please contact the sender or reply
to Enron Corp. at enron.messaging.administration@enron.com and delete all
copies of the message. This e-mail (and any attachments hereto) are not
intended to be an offer (or an acceptance) and do not create or evidence a
binding and enforceable contract between Enron Corp. (or any of its
affiliates) and the intended recipient or any other party, and may not be
relied on by anyone as the basis of a contract by estoppel or otherwise.
Thank you.
**********************************************************************