8 May 2001, 00:14 UTC
Eco Fuel Consumption
- From
- Paul Y'Barbo paul.y'barbo@enron.com
- Bcc
- Arthur Ransome
- Date
- Mon, 7 May 2001 17:14:00 -0700 (PDT)
Oscar, Per our conversation, the following are the fuel management team's assumptions of fuel requirements for Eco at 100% of capacity: LNG 91,260 MMBtu/day at 507 MW Heat Rate = 7500 BTU/kwh LPG 1905 Metric Tons at 507 MW Heat Rate = 7461 BTU/kwh (Note: 522 gallons/MT , 91,300 Btu/gallon) No.2 619,000 gallons/day at 465 MW Heat Rate = 7313 BTU/kwh (Note: 131,850 Btu/gallon) Heat rates at less than 100% of capacity will be different from those at 100%. Check with Rick or Arthur regarding performance curves. Call me if you have any additional questions. Regards, Paul