  1. 9 May 2000

    Bruce Golden to Benjamin Rogers

    Re: wps

    Ben Question 1 Case 1 at 20F and 60% RH CTG would have net unit output of 46,726 kW at a heat rate of 10,183 Btu/kWhr HHV new & clean Case 2 at 90F and 54% RH CTG would h…

  2. 9 May 2000

    Benjamin Rogers to Bruce Golden

    wps

    Hey Bruce, Oscar and I are looking to have the first 2 questions answered. If you could look at these and get back with me that would be great. I'm working on the 3rd que…

  3. 4 May 2000

    Benjamin Rogers to Bruce Golden

    Re: Plano vs Homestead

    Here is the e-mail that Bruce just sent me. Make sure that you do not use this for any binding agreements or client discussion purposes. These are the numbers I have used…

  4. 4 May 2000

    Bruce Golden

    Plano vs Homestead

    Ben This is a revised Plano we did late yesterday. It was adjusted from Lowell, Mass Nepco estimate and we changed format to more closely match Homestead form. Biggest di…

  5. 4 May 2000

    Bruce Golden to Benjamin Rogers

    Re: MHI 501G

    Ben This sure sounds like a deal Len Gunderson was looking at early this year and a large chemical facility. The capacity for the project did not match what equipment it …

  6. 4 May 2000

    Bruce Golden to Benjamin Rogers

    Re: MHI 501G

    Maybe the message is garbled but 4 7FA's and 2 STG's (probably two 2 X 1 CCGT's) should be nominally $470,000,000 based on the Pittsburg CCGT out in California (but inclu…

  7. 4 May 2000

    Benjamin Rogers to Bruce Golden

    Re: MHI 501G

    We are still looking for capital costs for a 730 MW plant in Texas, which comprises of 4 FA's and 2 STG's. We are currently using $450 MM for a total project cost number,…

  8. 3 May 2000

    Bruce Golden

    MHI 501G

    Ben Looks like a 2 X 1 MHI 501G plant would produce about 684MW plant net output at a heat rate of 6684 Btu/kWhr net new&clean. Still looking for capital cost. Bruce